Model 4001 Field Operation Test
   
[  ] Turn circuit breakers for all pool equipment off.
[  ]

The water level in the pool should be correct.
Verify the front panel switches are in the following positions:

Time Clock Off
Pump Off/Pump On Pump On
Manual/Auto Auto
Spa/Pool Pool
[  ]

Set Motor Control circuit board jumpers (located on the lower left part of the circuit board) as follows:
Note: See your manual for a detailed information on the board jumpers.

Flow Switch Bypass Normal
Test/Normal Test
3Hr/6Hr 3 Hour Position
Ht Pool Ht Pool & Spa (If pool and spa are to be heated.)
Ht Spa (If spa only is to be heated or if the heater is not connected to the controller.)
[  ] Turn circuit breakers on for all pool equipment.
The Mode light on the front panel should be red and blink.
No pumps should be running.
[  ] Turn the Manual/Auto switch to Manual for about 30 seconds.
The pump should run in high speed.
Return the switch to the Auto position.
[  ] Rotate the time clock to an On position.
The filter pump will run in high speed for about 15-30 seconds.
The front panel "No Flow" light will not illuminate.
[  ] After about 15-30 seconds the filter pump will switch to low speed.
The Pump Indicator on the front panel will be yellow.
[  ] Let the pump run in low speed for a couple of minutes.
The No Flow indicator on the front panel will not illuminate and the pump will stay in low speed.
[  ] Set the Manual/Auto switch to the Manual position.
The filter pump will run in high speed.
The heater, if connected to the system and the jumper on the circuit board is in the “heat pool & spa” position, will be allowed to fire.
The Pump Indicator on the front panel will be green.
[  ] Set the Manual /Auto switch to the Auto position.
The filter pump will run in low speed.
The heater, if connected, may or may not fire. This depends on the heater pressure switch setting and the circuit board jumper.
The Pump indicator on the front panel will be yellow or orange.
[  ] Turn the time clock to an off position.
The Cool Down light will illuminate if the jumper is in the “heat pool & spa” position. The filter pump will run for about 15-30 seconds.
The heater, if connected, will not fire.
[  ] The pump will turn off. The Pump light on the front panel will turn off.
[  ] Turn off all pool equipment circuit breakers.
[  ] Set the Motor Control circuit board Test/Normal jumper to Normal and set the other jumpers for normal operation.

  This completes the Field Operation Test.

   